Edwards EST

EST3

The Edwards EST3 is a large-scale life safety platform supporting fire alarm, mass notification, and building integration. One of the most widely installed panels in high-rise and campus applications.

11 manuals13 trouble codesModels: EST3, EST3X, EST3-1, EST3-2, EST3-4

Manuals

Manuals That Reference This Model (1)

Trouble Codes

View all 13
Tamper SwitchThe tamper switch has detected that the EST3X control panel door is open.Active Test TroubleA trouble is reported if devices are left in an active state after canceling a service group test.ALARMThe system has detected a fire or other life-threatening emergency condition.CPU FAILThe central processing unit has detected an internal processor failure.Dirty devices > 20%A smoke detector is beginning to accumulate dust and should be noted for future maintenance.Dirty Devices > 80%An addressable smoke detector has reached a high level of contamination and requires immediate cleaning or replacement.DISABLEA system component, such as a device, card, or group, has been manually taken out of service.GND FAULTThe SFS1-CPU module has detected an unintended connection between a system circuit and the earth ground.Preamp Supervision Module TroubleThe system has detected a fault in the preamp (line level) audio signals.MonitorSignals the operation of ancillary equipment, such as a fan feedback switch.

Specifications

SLC Loops
2 (per chassis)
Panel Type
Addressable
NAC Circuits
4 (per 3-LBUS module)
Total Points
500 (per chassis)
Network Nodes
64
Points/Loop
250
Battery (Ah)
7-200
Annunciator
Yes