ACTIVE
troubleNotifier NFS2-640
58 views·0 field notes
What This Code Means
The status banner displays ACTIVE when a monitor module programmed with a Trouble Monitor Type Code (such as AUDIO SYSTEM or POWER MONITR) is activated. These modules monitor external system functions that produce trouble signals.
Common Causes
- 1Fault in monitored audio equipment or amplifiers
- 2Power supply fault detected by a power monitor module
- 3Activation of a monitored system function that indicates a trouble condition
Resolution Steps
Press the ACKNOWLEDGE/SCROLL DISPLAY key to silence the panel sounder. Check the LCD display for the specific location and type of device reporting the trouble. Investigate and correct the condition causing the trouble in the monitored equipment. The panel will automatically return to normal once the condition is cleared, as these modules are non-latching.
Manual References(1)
Related Codes
Related Questions
What is the maximum device capacity on the NFS2-640 in FlashScan mode vs. CLIP mode, and can you mix protocols on the same SLC loop?How do I troubleshoot a ground fault on the NFS2-640 SLC loop?What are the NAC circuit specifications for the NFS2-640, and when do I need an external NAC booster panel?