CO TBL: NFS2-640 Trouble Code | Fire Alarm Resource Center
CO TBL
trouble
Notifier NFS2-640
65 views
·
0 field notes
What This Code Means
The CO element on a detector is not working properly.
Common Causes
1
CO element failure
2
Detector hardware malfunction
Resolution Steps
Replace the detector. Note that this trouble generates in FlashScan mode only; CLIP mode will generate a LO VAL error instead.
Manual References
(2)
1
notifier
NFS2-640
Operations
2013
p. 72
Open
2
notifier
NFS2-640
Datasheet
2017
Open
Getting CO TBL on your NFS2-640?
Ask TroubleShooter AI for help
→
Field Notes
Loading field notes...
Sign in
to share a field note
Related Codes
INVREP
The device has returned a response to the panel that the panel did not expect.
INST ON L1
No devices are installed on the system.
LO VAL
The detector chamber reading is too low, or the detector is not operating properly. In CLIP mode, this may also indicate a failure of the thermistors, CO element, or infra-red element, or a freeze warning.
PREALM
The control panel activates a Pre-Alarm Warning when a detector exceeds its programmed Pre-Alarm Alert or Action level, providing an early warning of incipient or potential fire conditions.
NETWORK FAIL PORT x
Communication lost between NCM Port x and corresponding node.
Related Questions
What is the maximum device capacity on the NFS2-640 in FlashScan mode vs. CLIP mode, and can you mix protocols on the same SLC loop?
How do I troubleshoot a ground fault on the NFS2-640 SLC loop?
What are the NAC circuit specifications for the NFS2-640, and when do I need an external NAC booster panel?