TROUBL CONTROL
troubleNotifier NFS2-640
55 views·0 field notes
What This Code Means
A trouble condition occurring on a control/relay module or control/relay transponder.
Common Causes
- 1Open circuit on the module's supervised wiring
- 2Short circuit on the module's supervised wiring
- 3Device not responding due to being disconnected or faulty
- 4Incorrect addressing on the SLC
Resolution Steps
Press the ACKNOWLEDGE/SCROLL DISPLAY key to silence the panel sounder. Check the connections from the module to the input or output device to which it is wired for opens or shorts. Determine whether the device is functional, connected, and addressed properly on the SLC.
Manual References(1)
Related Codes
Related Questions
What is the maximum device capacity on the NFS2-640 in FlashScan mode vs. CLIP mode, and can you mix protocols on the same SLC loop?How do I troubleshoot a ground fault on the NFS2-640 SLC loop?What are the NAC circuit specifications for the NFS2-640, and when do I need an external NAC booster panel?