PREALM
alarmNotifier NFS2-640
51 views·0 field notes
What This Code Means
A Pre-Alarm Warning indicates that a smoke detector has reached a programmed threshold (either Alert or Action level) that is below the actual alarm threshold, providing an early warning of potential fire conditions.
Common Causes
- 1Incipient or potential fire conditions
- 2Dust or dirt accumulation in the detector chamber
- 3Transient noise or electrical interference
- 4Environmental factors such as steam or aerosols
- 5High sensitivity settings (Self-Optimizing Pre-Alarm)
Resolution Steps
Identify the device location from the LCD display and investigate the area for signs of smoke or fire. Check the real-time smoke level percentage shown on the LCD. If the condition is an 'Alert' (non-latching), it will clear automatically when smoke levels drop. If it is an 'Action' (latching), press the RESET key after the condition has been cleared. Press ACKNOWLEDGE to silence the panel sounder.
Manual References(1)
Related Codes
Related Questions
What is the maximum device capacity on the NFS2-640 in FlashScan mode vs. CLIP mode, and can you mix protocols on the same SLC loop?How do I troubleshoot a ground fault on the NFS2-640 SLC loop?What are the NAC circuit specifications for the NFS2-640, and when do I need an external NAC booster panel?