PREALMalarm
Notifier NFS2-640: PREALM
Notifier NFS2-640·0 views·0 field notes
What This Code Means
A Pre-Alarm Warning indicates that a smoke detector has reached a programmed threshold (either Alert or Action level) that is below the actual alarm threshold, providing an early warning of potential fire conditions.
Common Causes
- 1Incipient or potential fire conditions
- 2Dust or dirt accumulation in the detector chamber
- 3Transient noise or electrical interference
- 4Environmental factors such as steam or aerosols
- 5High sensitivity settings (Self-Optimizing Pre-Alarm)
Resolution Steps
Identify the device location from the LCD display and investigate the area for signs of smoke or fire. Check the real-time smoke level percentage shown on the LCD. If the condition is an 'Alert' (non-latching), it will clear automatically when smoke levels drop. If it is an 'Action' (latching), press the RESET key after the condition has been cleared. Press ACKNOWLEDGE to silence the panel sounder.