What This Code Means

A Pre-Alarm Warning indicates that a smoke detector has reached a programmed threshold (either Alert or Action level) that is below the actual alarm threshold, providing an early warning of potential fire conditions.

Common Causes

  • 1Incipient or potential fire conditions
  • 2Dust or dirt accumulation in the detector chamber
  • 3Transient noise or electrical interference
  • 4Environmental factors such as steam or aerosols
  • 5High sensitivity settings (Self-Optimizing Pre-Alarm)

Resolution Steps

Identify the device location from the LCD display and investigate the area for signs of smoke or fire. Check the real-time smoke level percentage shown on the LCD. If the condition is an 'Alert' (non-latching), it will clear automatically when smoke levels drop. If it is an 'Action' (latching), press the RESET key after the condition has been cleared. Press ACKNOWLEDGE to silence the panel sounder.