STYLE 6 POS. LOOP x
troubleNotifier NFS2-640
61 views·0 field notes
What This Code Means
There is an open circuit on the positive side of loop x.
Common Causes
- 1Open circuit on the positive side of the SLC loop
Resolution Steps
Correct the open circuit condition on the positive side of the loop and press the RESET button. Note that Style 6 and Style 7 are supervised methods, and the panel will drive both ends of the loop in an unsupervised method until the latching trouble is cleared.
Manual References(1)
Related Codes
Related Questions
What is the maximum device capacity on the NFS2-640 in FlashScan mode vs. CLIP mode, and can you mix protocols on the same SLC loop?How do I troubleshoot a ground fault on the NFS2-640 SLC loop?What are the NAC circuit specifications for the NFS2-640, and when do I need an external NAC booster panel?