STYLE 6 SHORT LOOP xtrouble
Notifier NFS2-640: STYLE 6 SHORT LOOP x
Notifier NFS2-640·0 views·0 field notes
What This Code Means
The control panel has detected a short circuit on the SLC loop configured for Style 6 or Style 7. The panel is driving both ends of the loop to maintain communication in an unsupervised method.
Common Causes
- 1Short circuit on the SLC loop wiring
- 2Faulty addressable device
- 3Incorrect wiring of ISO-X isolator modules
Resolution Steps
Locate and correct the short circuit condition on the SLC loop, then press the RESET button to clear the latching trouble. Ensure ISO-X isolator modules are used if the system is configured for Style 7.