Honeywell

VISTA-128FBP

The Honeywell VISTA-128FBP is a commercial fire alarm panel supporting up to 128 zones. Commonly found in small to medium commercial fire alarm applications.

2 manuals27 trouble codesModels: VISTA-128FBP, VISTA-128FBPT, VISTA-250FBP, VISTA-250FBPT

Manuals

Trouble Codes

View all 27
CHECK or TRBL 6XXIndicates a trouble condition on a supervised relay where XX is the relay number (01-32).CHECK or TRBL 8XXIndicates a trouble on a peripheral device connected to the panel's keypad terminals where XX is the device address (00-30).CHECK or TRBL 970Trouble detected on Bell 1 Output (Notification Appliance Circuit).CHECK or TRBL 971Trouble detected on Bell 2 Output (Notification Appliance Circuit).972 Earth Ground FaultA system trouble indicating that an earth ground fault has been detected. This condition may eliminate some of the system's protection.CHECK or TRBL 973Trouble detected on the J2 Trigger Output.CHECK or TRBL 974Trouble detected on Dialer 1.CHECK or TRBL 975Trouble detected on Dialer 2.CHECK or TRBL 988The 2nd RF Receiver is not receiving signals.CHECK or TRBL 990The 1st RF Receiver is not receiving signals.

Specifications

SLC Loops
N/A (V-Plex Polling Loop)
Panel Type
Hybrid (Security/Fire)
IDC Zones
128 (hardwired + V-Plex)
NAC Circuits
2
Battery (Ah)
4-14