972 Earth Ground Faulttrouble
Honeywell VISTA-128FBP: 972 Earth Ground Fault
Honeywell VISTA-128FBP·1 view·0 field notes
What This Code Means
A system trouble indicating that an earth ground fault has been detected. This condition may eliminate some of the system's protection.
Common Causes
- 1Electrical ground connections of the power utility, telephone lines and internal metallic water pipe system are not connected together
- 2Electrical surges, typically lighting transients
- 3Equipment malfunctions or unauthorized repairs or alterations
Resolution Steps
Determine if the zone(s) displayed are intact and make them so if they are not. If the problem has been corrected, key an OFF sequence (Code plus OFF) to clear the “CHECK” or “TRBL” display. If the display persists, CALL FOR SERVICE IMMEDIATELY. Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or electrician, as appropriate.
Manual References(1)
Related Codes
Related Questions
How are the VISTA-128FBP bell output circuits wired and what supervision method does the system use to detect an open or short?How does the VISTA-128FBP supervise its backup battery and what does a battery trouble condition indicate?What does a ground fault trouble indicate on the VISTA-128FBP and how do I locate it?