VISTA-128FBP Trouble Codes

27 trouble codes for the Honeywell VISTA-128FBP

CHECK or TRBL 6XX
Indicates a trouble condition on a supervised relay where XX is the relay number (01-32).
trouble
CHECK or TRBL 8XX
Indicates a trouble on a peripheral device connected to the panel's keypad terminals where XX is the device address (00-30).
trouble
CHECK or TRBL 970
Trouble detected on Bell 1 Output (Notification Appliance Circuit).
trouble
CHECK or TRBL 971
Trouble detected on Bell 2 Output (Notification Appliance Circuit).
trouble
972 Earth Ground Fault
A system trouble indicating that an earth ground fault has been detected. This condition may eliminate some of the system's protection.
trouble
CHECK or TRBL 973
Trouble detected on the J2 Trigger Output.
trouble
CHECK or TRBL 974
Trouble detected on Dialer 1.
trouble
CHECK or TRBL 975
Trouble detected on Dialer 2.
trouble
CHECK or TRBL 988
The 2nd RF Receiver is not receiving signals.
trouble
CHECK or TRBL 990
The 1st RF Receiver is not receiving signals.
trouble
CHECK or TRBL 997
Polling Loop Short circuit detected.
trouble
AC LOSS
The system has lost primary AC power and the keypad is operating on battery power only.
trouble
ALARM
Indicates that a burglary or non-fire protection zone has been faulted while the system is armed, or a 24-hour zone has been triggered.
alarm
CHECK or TRBL CALL SERVICE
A problem exists with the system that eliminates some of the protection.
trouble
CHECK
Indicates a trouble condition in the system, which may be associated with specific zones, supervised relays, peripheral devices, or system components like dialers and ground faults.
trouble
CHECK or TRBL
Indicates a trouble condition in the system, meaning a problem exists with specific zones, relays, peripheral devices, or system components that may eliminate some protection.
trouble
CHECK or TRBL accompanied by zone descriptor
A problem exists with the specific zone(s) displayed, which may include Fire or Waterflow zones.
trouble
COMM. FAILURE
A failure has occurred in the telephone communication portion of the system.
trouble
FIRE
A fire emergency has been detected by smoke or heat detectors, or has been manually initiated via a panic key.
alarm
FIRE DRILL ACTIVE
The system is currently in Fire Drill test mode.
maintenance
HSENS accompanied by zone number
A smoke detector has a high sensitivity level, which may cause false alarms.
maintenance
LO BAT accompanied by zone descriptor
A low battery condition exists in the displayed wireless transmitter.
trouble
LSENS accompanied by zone number
A smoke detector has a low sensitivity level and might not detect smoke.
maintenance
FIRE or ALARM accompanied by zone descriptor
Indicates that an alarm occurred while the system was armed.
alarm
MODEM COMM
The control panel is currently communicating with the central station's remote computer.
maintenance
SUPV
This display indicates a problem on fire supervisory zone(s), which means that the operation of the fire alarm system may be compromised.
supervisory
SYSTEM LO BAT
The system's main backup battery is low.
trouble