bad type fault
trouble

Edwards EST EST4

68 views·0 field notes

What This Code Means

This condition occurs when a substituted device is a different model than the suspect device but is preprogrammed with the same device address.

Common Causes

  • 1Substituted device is a different model than the suspect device
  • 2Device preprogrammed with the same address as a different model
  • 3Incorrect device model installed during replacement

Resolution Steps

To remove the fault, you must accept the model of the known good device using the 4-CU or replace the substituted device with a model that matches the suspect device.