Ground Faulttrouble

Kidde FX-5: Ground Fault

Kidde FX-5·0 views·0 field notes

What This Code Means

The panel detected an unintended electrical path between the system wiring and earth ground.

Common Causes

  • 1Pinched wire in a junction box
  • 2Moisture in conduit or devices
  • 3Damaged wire insulation touching the cabinet

Resolution Steps

Systematically disconnect field circuits (IDCs, NACs, etc.) one at a time until the ground fault clears. Once the circuit is identified, trace the wiring to find the point of contact with ground.