Ground Fault: FX-5 Trouble Code | Fire Alarm Resource Center
Ground Fault
trouble
Kidde FX-5
66 views·0 field notes
What This Code Means
The panel detected an unintended electrical path between the system wiring and earth ground.
Common Causes
1Pinched wire in a junction box
2Moisture in conduit or devices
3Damaged wire insulation touching the cabinet
Resolution Steps
Systematically disconnect field circuits (IDCs, NACs, etc.) one at a time until the ground fault clears. Once the circuit is identified, trace the wiring to find the point of contact with ground.