Ground Faulttrouble
Kidde FX-5: Ground Fault
Kidde FX-5·0 views·0 field notes
What This Code Means
The panel detected an unintended electrical path between the system wiring and earth ground.
Common Causes
- 1Pinched wire in a junction box
- 2Moisture in conduit or devices
- 3Damaged wire insulation touching the cabinet
Resolution Steps
Systematically disconnect field circuits (IDCs, NACs, etc.) one at a time until the ground fault clears. Once the circuit is identified, trace the wiring to find the point of contact with ground.