Ground Fault
troubleKidde FX-5
50 views·0 field notes
What This Code Means
The panel detected an unintended electrical path between the system wiring and earth ground.
Common Causes
- 1Pinched wire in a junction box
- 2Moisture in conduit or devices
- 3Damaged wire insulation touching the cabinet
Resolution Steps
Systematically disconnect field circuits (IDCs, NACs, etc.) one at a time until the ground fault clears. Once the circuit is identified, trace the wiring to find the point of contact with ground.
Manual References(2)
Related Codes
Related Questions
Why does my FX-5 show a NAC circuit trouble even though all appliances are wired and the EOL resistor is installed?How do I clear a ground fault trouble on the Kidde FX-5 when the Ground Fault LED stays lit?What battery size fits inside the FX-5 cabinet, and what is the maximum Ah rating the charger can support?