What This Code Means

The control panel indicates that a specific detector, monitor module, control/relay module, or panel circuit module has been disabled and will not cause an alarm or any Control-by-event activity.

Common Causes

  • 1Manual disablement of a detector, monitor module, or control/relay module
  • 2A zone being disabled, which disables all mapped input and output devices if it is their primary zone
  • 3Manual disablement of a Panel Circuit module

Resolution Steps

Press the ACKNOWLEDGE soft key to silence the panel sounder and switch the SYSTEM TROUBLE LED from flashing to steady. To restore the point to service, access the PROGRAM/ALTER STATUS menu (password required) to re-enable the specific point or zone.