NFS2-3030 Trouble Codes
57 trouble codes for the Notifier NFS2-3030
ADV WALK TESTANNUN x NO ANSWERANNUN x TROUBLEAUXILIARY TROUBLEBASIC WALK TESTBEAM BLOCKEDBRAND MISMATCHBUZZER OFFCHARGER FAULTCLASS A FAULTCO 6 MONTHSCO EXPIREDCOMM LOSSCONFIGURATIONCORRUPT LOGIC EQUATCO TROUBLEDISABLEDDRILL INITIATEDEPROM ERROREXTERNAL RAM ERRORGROUND FAULTGROUND FAULT LOOP xINTERNAL RAM ERRORLOADING..NO SERVICELOOP x- x COMM FAILUREMANUAL MODE ENTEREDMISMAT HDWE TYPEMOD EXT PWER LOSSNCM COMM LOSSNETWORK FAIL PORT xNETWORK INCOMPATIBILITYNFPA 24HR REMINDERNO ANSWERINST ON L1NO POWER SUPPLY INSTNVRAM BATT TROUBLEOPEN CIRCUITPANEL DOOR OPENPRINTER OFF LINEPRINTER PAPER OUTPROG MODE ACTIVATEDPROGRAM CORRUPTEDREMOTE DISPLAY x NO ANSWERREMOTE DISPLAY x TROUBLERFX COMM LOSSSECURITY TAMPERSELF TEST FAILEDSHORT CIRCUITSOFTWARE MISMATCHSTYLE 4 SHORT x LOOP xSTYLE 6 NEG LOOP xSTYLE 6 POS LOOP xSTYLE 6 SHORT LOOP xSUPERVISORYTAMPERVERIFY OVER MAXWATERFLOW S
An Advanced Walk Test is currently in progress on the system.
maintenance
The annunciator at the specified address (x) is not responding to the control panel.
trouble
The annunciator at the specified address (x) is reporting an internal trouble condition.
trouble
An auxiliary device connected to the CPU at J5 is in trouble or the connection cable is missing.
trouble
A Basic Walk Test is currently in progress.
maintenance
The path between a beam detector and its reflector is obstructed.
trouble
The brand of the SLC device is incompatible with the FACP.
trouble
The DVC's local piezo buzzer is disabled.
trouble
The battery charger in the power supply is not functioning.
trouble
A wireless device is missing its redundant Class A connection.
trouble
The CO detection element in a detector has six months remaining before expiration.
maintenance
The CO detection element in a detector has reached the end of its life.
trouble
Communication lost between an FMM-4-20 module and its sensor.
trouble
A problem occurred after sending configuration from PipeIQ to a FAAST detector.
trouble
The database containing the panel's logic equations is corrupted.
trouble
The CO element on a detector is not working properly.
trouble
The control panel indicates that a specific detector, monitor module, control/relay module, or panel circuit module has been disabled and will not cause an alarm or any Control-by-event activity.
trouble
A fire drill has been started locally at the panel.
maintenance
The application or boot code stored in EPROM is corrupt.
trouble
The panel's external RAM test has failed.
trouble
A ground fault condition has been detected on the main, auxiliary, or DAL device power supply, or within the panel itself.
trouble
A ground fault has been detected on SLC loop x.
trouble
The panel's internal RAM test has failed.
trouble
A program or database download is in progress, and the panel is not providing fire protection.
maintenance
Communication has failed for the specified pair of loops.
trouble
An annunciator has been manually placed into a non-normal mode.
trouble
The programmed device type does not match the physical device at the address.
trouble
A control module has lost its external power source.
trouble
Communication is lost between the CPU-3030 and the Network Communications Module (NCM).
trouble
Communication lost between NCM Port x and the corresponding network node.
trouble
The panel brand or product version is incompatible with the current network.
trouble
Daily reminder occurring at 11 am if any troubles remain unresolved on the system.
trouble
A device (module or detector) is not responding to the panel's poll.
trouble
The system detects that no devices are installed on Loop 1.
trouble
The address of the main power supply (AMPS-24) has not been correctly entered in programming.
trouble
The battery backup for the NVRAM or the system clock is low.
trouble
The module device has an open circuit on its supervised wiring.
trouble
The main panel cabinet door is open.
trouble
Communication loss with the system printer.
trouble
The system printer has run out of paper.
trouble
A user is currently accessing the panel's programming menus.
maintenance
The panel's programming database is corrupt.
trouble
The remote display at address x is not responding.
trouble
The remote display at address x is reporting a trouble condition.
trouble
Communication has been lost with an RFX wireless device.
trouble
An RFX device has been removed from its base or tampered with.
supervisory
An internal diagnostic self-test has failed.
trouble
A module has detected a short circuit on its supervised wiring.
trouble
Incompatible software revisions detected between system modules.
trouble
A short circuit has been detected on a Style 4 SLC loop.
trouble
A short circuit exists on the negative side of SLC loop x.
trouble
A short circuit exists on the positive side of SLC loop x.
trouble
A short circuit has been detected on a Style 6 SLC loop.
trouble
The system indicates a Supervisory alarm when a monitor module point programmed with a supervisory Type Code activates, such as a sprinkler valve tamper condition.
supervisory
A monitor module point programmed with this Type ID code has activated, typically indicating that the module is connected to a tamper switch that has been triggered.
supervisory
A device has exceeded its alarm verification limit without entering a full alarm state.
trouble
A latching supervisory condition indicating that a monitor module set to monitor waterflow (such as a sprinkler system) has been activated.
supervisory