WATERFLOW S: NFS2-3030 Trouble Code | Fire Alarm Resource Center
WATERFLOW S
supervisory
Notifier NFS2-3030
67 views·0 field notes
What This Code Means
A latching supervisory condition indicating that a monitor module set to monitor waterflow (such as a sprinkler system) has been activated.
Common Causes
1Activation of a waterflow switch
2Sprinkler system activation
3Triggering of a monitor module programmed with a waterflow type code
Resolution Steps
Investigate and correct the condition causing the Supervisory. Press the SYSTEM RESET soft key to clear the condition, as WATERFLOW S is a latching type code and will not automatically clear when the condition causing its activation disappears.