PREALMsupervisory
Notifier NFS2-640: PREALM
Notifier NFS2-640·0 views·0 field notes
What This Code Means
The control panel activates a Pre-Alarm Warning when a detector exceeds its programmed Pre-Alarm Alert or Action level, providing an early warning of incipient or potential fire conditions.
Common Causes
- 1Smoke or heat levels reaching the programmed pre-alarm threshold
- 2Dust or dirt accumulation in the detector
- 3Environmental transients or electrical interference
- 4Incipient fire condition
Resolution Steps
Identify the device address and location from the LCD display. Investigate the specified area for signs of fire or smoke. If no fire is present, inspect the detector for contamination or dust. For 'Alert' (non-latching) conditions, the status will clear automatically when smoke levels drop; for 'Action' (latching) conditions, the system must be reset after the condition is cleared.