Missingtrouble

Silent Knight 5820XL: Missing

Silent Knight 5820XL·1 view·0 field notes

What This Code Means

SLC devices are not being recognized by the control panel, indicating a communication failure with a programmed device.

Common Causes

  • 1Incorrect hardware connections or wiring polarity
  • 2SLC devices addressed improperly
  • 3Devices connected to SLC IN terminals instead of SLC OUT
  • 4SLC loop impedance is outside the required range

Resolution Steps

Check hardware connections. If devices are physically connected, make sure wiring is correct. For the main panel, the positive side of device must be connected to terminal 34; the negative side must be connected to Terminal 33. For 5815XL devices, make sure the device connects to the 5815XL via the SLC OUT terminals. Do not connect devices to terminals labeled SLC IN. Make sure SLC devices have been addressed properly. Check that SLC loop impedance is within the required range.