Silent Knight

SK-5207

The Silent Knight 5207 is a small addressable fire alarm control panel supporting 1 SLC loop. A cost-effective solution for small commercial applications.

3 manuals33 trouble codesModels: 5207, SK-5207, 5207-4

Manuals

Manuals That Reference This Model (3)

Trouble Codes

View all 33
A1Indicates a trouble condition on notification circuit 1 (bell output 1) or that the power supply and panel voltage selections are not the same.Trouble with specified bell outputA trouble condition exists on the indicated notification (bell) circuit.A2A trouble condition exists on notification circuit 2 (bell output 2), or the power supply and panel voltage selections are not the same.A3Indicates a trouble condition on notification circuit 3 or that the power supply and panel voltage selections are not the same.A4A trouble condition exists on notification circuit (bell) number 4, or the power supply and panel voltage selections do not match.ACThe panel has detected a low AC condition or AC power has been lost.BUS TROUBLEThe annunciator data wires are shorted or reversed.dCThe panel has detected a low battery condition.FAILED DFThe communicator has failed to report an event to the central station after the programmed number of attempts have been made.DISABLED: ZONE #A zone has been manually disabled or bypassed.

Specifications

SLC Loops
N/A (Conventional)
Panel Type
Conventional
IDC Zones
8 (expandable to 16)
NAC Circuits
4 Style Y
Battery (Ah)
17-34