What This Code Means

The communicator has failed to report an event to the central station after the programmed number of attempts have been made.

Common Causes

  • 1Communicator failed to reach the central station after programmed number of attempts
  • 2Phone line voltage dropped below 3 VDC
  • 3Central station receiver not acknowledging the call

Resolution Steps

Reset the dialer by pressing 3 ENTER + code 0 or 1. Check phone line connections and ensure the phone lines are programmed properly.