SK-5207 Trouble Codes
33 trouble codes for the Silent Knight SK-5207
A1Trouble with specified bell outputA2A3A4ACBUS TROUBLEdCFAILED DFDISABLED: ZONE #DATA LOSTE0E7BUS TROUBLEF1Trouble with specified annunciator (1-7)F2F3HEAT TROUBLE 1-16L1Phone line faultL2P0P1ACCESSORY POWERP3P4DATA LOSTREMOTE PROG. FAIL1-16 Sprinkler supervisory troubleUNDEFINED TROUBLE 1-16WATER TROUBLE 1-16COLD TROUBLE 1-16
Indicates a trouble condition on notification circuit 1 (bell output 1) or that the power supply and panel voltage selections are not the same.
trouble
A trouble condition exists on the indicated notification (bell) circuit.
trouble
A trouble condition exists on notification circuit 2 (bell output 2), or the power supply and panel voltage selections are not the same.
trouble
Indicates a trouble condition on notification circuit 3 or that the power supply and panel voltage selections are not the same.
trouble
A trouble condition exists on notification circuit (bell) number 4, or the power supply and panel voltage selections do not match.
trouble
The panel has detected a low AC condition or AC power has been lost.
trouble
The annunciator data wires are shorted or reversed.
trouble
The panel has detected a low battery condition.
trouble
The communicator has failed to report an event to the central station after the programmed number of attempts have been made.
trouble
A zone has been manually disabled or bypassed.
maintenance
The communicator has lost data that was being transmitted to the central station, or the alarm memory buffer is full.
trouble
This code indicates a trouble condition with the system's built-in digital dialer/communicator.
trouble
This code indicates a trouble condition with the panel's EEPROM (Electrically Erasable Programmable Read-Only Memory).
trouble
This code indicates a bus trouble or power trouble specifically related to the 5230 remote annunciator.
trouble
This code indicates a trouble condition with remote annunciator number 1.
trouble
Trouble with a specific annunciator (ID 1-7).
trouble
A trouble condition exists on the second remote annunciator (Model 5230) connected to the system.
trouble
This code indicates a trouble condition with remote annunciator number 3 on the system bus.
trouble
Trouble condition in heat zone 1-16.
trouble
A trouble condition or fault exists on phone line 1.
trouble
A trouble condition exists on the indicated phone line.
trouble
A trouble condition or fault exists on phone line 2.
trouble
The built-in touchpad displays this code to indicate that the system printer is out of paper.
trouble
The panel has detected a trouble condition with the smoke detector power supply.
trouble
Indicates a trouble condition with the accessory power at terminal 26 or a mismatch between the power supply and panel voltage selections.
trouble
The panel has detected a short between earth ground (terminal 52) and circuit ground (terminals 1, 10, 20, 25).
trouble
The panel has detected a short between any power source and earth ground.
trouble
Previous event could not be reported and the information was lost.
trouble
Problem with downloading; data transfer did not complete successfully.
trouble
A trouble condition exists on a sprinkler supervisory zone.
supervisory
Trouble condition in auxiliary zone 1-16.
trouble
Trouble condition in water zone 1-16.
trouble
Trouble condition in cold zone 1-16.
trouble