A2: SK-5207 Trouble Code | Fire Alarm Resource Center
A2
trouble
Silent Knight SK-5207
125 views·0 field notes
What This Code Means
A trouble condition exists on notification circuit 2 (bell output 2), or the power supply and panel voltage selections are not the same.
Common Causes
1Trouble condition on notification circuit 2
2Power supply and panel voltage selections are not the same
3Open or short circuit in bell output wiring
Resolution Steps
Verify that the power supply and panel voltage selections are the same in programming step 2. Use Mode 25 (Accu-Zone Troubleshooting) to locate and correct the condition on the notification circuit.