A2trouble
Silent Knight SK-5207: A2
Silent Knight SK-5207·0 views·0 field notes
What This Code Means
A trouble condition exists on notification circuit 2 (bell output 2), or the power supply and panel voltage selections are not the same.
Common Causes
- 1Trouble condition on notification circuit 2
- 2Power supply and panel voltage selections are not the same
- 3Open or short circuit in bell output wiring
Resolution Steps
Verify that the power supply and panel voltage selections are the same in programming step 2. Use Mode 25 (Accu-Zone Troubleshooting) to locate and correct the condition on the notification circuit.