Fire-Lite MS-9200UDLS: DISABL

Fire-Lite MS-9200UDLS·1 view·0 field notes

What This Code Means

A point (detector or module) has been manually deactivated in the system programming, which causes a system trouble condition until the point is re-enabled.

Common Causes

  • 1Manual deactivation of a device for maintenance or testing
  • 2A device was disabled to prevent nuisance alarms from a known faulty sensor
  • 3A control point was disabled to prevent output activation during system testing

Resolution Steps

Access the Programming mode by pressing ENTER and entering the Level 2 password. Select the 'DISABLE/ENABLE' option. Press the * key for detectors or # key for modules, followed by the device address, then press ENTER. Use the UP or DOWN arrow keys to change the status label from DISABL back to ENABLE. Press ENTER to store the change in memory. Press the RESET key to clear the trouble condition.