What This Code Means
A fault condition (open or short) has been detected on Notification Appliance Circuit 2.
Common Causes
- 1Missing 4.7K ohm EOL resistor
- 2Broken circuit wiring
- 3Short in a notification appliance
Resolution Steps
Check for the presence of the 4.7K ohm EOL resistor at the end of the circuit. Inspect wiring for opens or shorts.