AC Fail or Brownouttrouble

Siemens MXL: AC Fail or Brownout

Siemens MXL·0 views·0 field notes

What This Code Means

Primary AC power is missing or below the brownout level; the System is running on battery backup.

Common Causes

  • 1Primary AC power is missing
  • 2AC power is below the brownout level
  • 3Blown fuses F1 or F2 on the SMB-2
  • 4Tripped circuit breaker on the MPS-6
  • 5Faulty AC or battery wiring

Resolution Steps

Check AC and battery. Check fuses F1 and F2 on the SMB-2 and the circuit breaker on the MPS-6. Check AC and battery wiring. If power connections are OK, check the cable between the SMB-2 and MKB-4 for proper installation.