AC Fail or Brownout: MXL Trouble Code | Fire Alarm Resource Center
AC Fail or Brownout
trouble
Siemens MXL
89 views·0 field notes
What This Code Means
Primary AC power is missing or below the brownout level; the System is running on battery backup.
Common Causes
1Primary AC power is missing
2AC power is below the brownout level
3Blown fuses F1 or F2 on the SMB-2
4Tripped circuit breaker on the MPS-6
5Faulty AC or battery wiring
Resolution Steps
Check AC and battery. Check fuses F1 and F2 on the SMB-2 and the circuit breaker on the MPS-6. Check AC and battery wiring. If power connections are OK, check the cable between the SMB-2 and MKB-4 for proper installation.