AC Fail or Brownout
troubleSiemens MXL
66 views·0 field notes
What This Code Means
Primary AC power is missing or below the brownout level; the System is running on battery backup.
Common Causes
- 1Primary AC power is missing
- 2AC power is below the brownout level
- 3Blown fuses F1 or F2 on the SMB-2
- 4Tripped circuit breaker on the MPS-6
- 5Faulty AC or battery wiring
Resolution Steps
Check AC and battery. Check fuses F1 and F2 on the SMB-2 and the circuit breaker on the MPS-6. Check AC and battery wiring. If power connections are OK, check the cable between the SMB-2 and MKB-4 for proper installation.
Manual References(1)
Related Codes
Related Questions
What modules are available to expand the MXL beyond its base configuration, and what is the maximum supported cabinet and loop count?What are the battery requirements and backup power calculations for the MXL?What is the purpose of the BCM-12A-C battery charger module on the MXL, and how many batteries does it support?