Simplex

4010ES

The Simplex 4010ES is a mid-size addressable fire alarm panel. A popular choice for small to medium commercial applications requiring Simplex reliability.

7 manuals41 trouble codesModels: 4010ES, 4010, 4010-9521, 4010-9522, 4010ES-1

Manuals

Manuals That Reference This Model (19)

Trouble Codes

View all 41
4009 NAC Power FailureOne or more NACs on a 4009 IDNet NAC Extender has a power failure.Abort Switch ActiveAn abort switch has been activated, preventing the release of suppression agents.Almost DirtyThe TrueAlarm sensor is accumulating dust and is approaching the threshold where it will require cleaning.IDNet Device: M#-# Battery FaultThis trouble indicates that there is a battery failure on the 4009 IDNet NAC Extender device connected to the system.Battery Standby TroubleThe system backup batteries are low, missing, or failed.Crash Code [Message]An unrecoverable software error has occurred.System Time and DateThe system time and date are incorrect.Simplex ServiceThe panel is in Service Mode.Active List OverflowThe number of active alarms, supervisories, or troubles exceeds the system's list capacity.City DisconnectThe city circuit has been disconnected.

Specifications

SLC Loops
1 (expandable)
Panel Type
Addressable
NAC Circuits
4 Class A or B
Total Points
1,000
Network Nodes
64
Points/Loop
250
Battery (Ah)
7-110
Annunciator
Yes