The primary differences between the NFS-320 and NFS2-640 are loop capacity and physical assembly. The NFS2-640 is a modular system that supports one SLC loop...
Yes, the NFS-320 is networkable on NOTI-FIRE-NET in both standard and high-speed configurations [1]. Each panel requires either a Network Communication Module...
The NFS-320 performs automatic detector sensitivity tests every 256 minutes, while the Walk Test uses detector LEDs to provide diagnostic feedback. During a...
The NFS-320 uses two 12-volt BAT Series batteries with a capacity ranging from 18 AH to 200 AH (Page 4) [1]. An external battery box is required for any...
The NFS-320 supports several communicator options, including the UDACT (dual phone line), 411/411UDAC series, IPDACT-2/2UD (Internet), and IPGSM-4G or...
You can program the NFS-320 using the Autoprogram routine, the front panel keypad (with KDM-R2), or VeriFire Tools software [1]. While the keypad allows for...
The NFS-320 features four built-in Notification Appliance Circuits (NACs) that can be configured for Class A (Style Z) or Class B (Style Y) operation (Page 25)...
The NFS-320 SLC loop supports a maximum of 318 points, split between 159 intelligent detectors and 159 monitor or control modules (Page 34) [1]. I could not...
The INVREP trouble indicates that a device has returned a response to the panel that the panel did not recognize (Page 68) [1]. When this occurs after...