AC LOSStrouble
Fire-Lite MS-9600: AC LOSS
Fire-Lite MS-9600·1 view·0 field notes
What This Code Means
The control panel has lost its primary AC power supply and is currently operating on standby batteries.
Common Causes
- 1Loss of primary AC power from the branch circuit
- 2Tripped or turned off branch circuit breaker
- 3Loose or disconnected AC wiring at terminal block TB1
Resolution Steps
Check the primary AC power source and branch circuit breaker. Verify that 120 VAC or 240 VAC is present at terminal block TB1. Ensure the green AC Power LED is illuminated once power is restored.