MS-9600 Trouble Codes

18 trouble codes for the Fire-Lite MS-9600

AC LOSS
The control panel has lost its primary AC power supply and is currently operating on standby batteries.
trouble
AC Power
The control panel has lost its primary 120VAC or 240VAC power source.
trouble
ACTIVE SUPERVISORY
A condition indicating a state that needs attention but is not an alarm, such as a sprinkler valve tamper condition.
supervisory
ALARM SILENCED
This condition indicates that the notification appliance circuits (NACs) have been manually turned off by pressing the Alarm Silence key while an alarm condition is still active.
trouble
AUTO TEST FAIL
A smoke detector failed its automatic functional test performed by the panel every two hours.
trouble
Battery Fault
The system has detected an issue with the standby batteries or their connection.
trouble
Charger Fault
The internal battery charging circuit is not functioning correctly.
trouble
DISABL
Indicates that a zone, NAC, detector, or module has been temporarily disabled in programming by the user.
trouble
Duplicate Address
The system has detected more than one device sharing the same SLC address.
trouble
EARTH FAULT
A ground fault condition indicating zero impedance between the Fire Alarm Control Panel and ground.
trouble
GROUND FAULT
This condition indicates a ground fault, specifically zero impedance between the Fire Alarm Control Panel (FACP) and ground.
trouble
Maintenance Alert
A smoke detector has accumulated enough dust or dirt to potentially cause a false alarm.
maintenance
NAC Fault
A problem has been detected on one of the Notification Appliance Circuits.
trouble
OPEN
This condition indicates an open circuit on an addressable device (smoke detector, monitor module, or control module) connected to the Signaling Line Circuit (SLC) loop.
trouble
Program Check
The system has identified a logical error in the site programming.
trouble
Sprinkler Supervisory
A condition monitoring the sprinkler system's readiness has been triggered.
supervisory
Type-Code Mismatch
The physical device installed at an address does not match the device type defined in the panel's memory.
trouble
Waterflow
The system has detected water movement in the sprinkler piping, indicating a possible fire or leak.
supervisory