DISABLtrouble

Fire-Lite MS-9600: DISABL

Fire-Lite MS-9600·1 view·0 field notes

What This Code Means

Indicates that a zone, NAC, detector, or module has been temporarily disabled in programming by the user.

Common Causes

  • 1A software zone has been manually disabled
  • 2An addressable detector has been manually disabled
  • 3An addressable module has been manually disabled
  • 4A Notification Appliance Circuit (NAC) has been manually disabled

Resolution Steps

Access the Maintenance Programming mode by pressing the Enter key, then press 2 and enter the Maintenance level password (default 11111). To enable a point, press 1 for Point Program, select the Loop, select the device type (detector or module), enter the three-digit device address, and change the status to enabled. To enable a zone, navigate to Zone Setup and select the zone number to be enabled.

Manual References(3)