DISABL: MS-9600 Trouble Code | Fire Alarm Resource Center
DISABL
trouble
Fire-Lite MS-9600
96 views·0 field notes
What This Code Means
Indicates that a zone, NAC, detector, or module has been temporarily disabled in programming by the user.
Common Causes
1A software zone has been manually disabled
2An addressable detector has been manually disabled
3An addressable module has been manually disabled
4A Notification Appliance Circuit (NAC) has been manually disabled
Resolution Steps
Access the Maintenance Programming mode by pressing the Enter key, then press 2 and enter the Maintenance level password (default 11111). To enable a point, press 1 for Point Program, select the Loop, select the device type (detector or module), enter the three-digit device address, and change the status to enabled. To enable a zone, navigate to Zone Setup and select the zone number to be enabled.