EARTH FAULTtrouble

Fire-Lite MS-9600: EARTH FAULT

Fire-Lite MS-9600·2 views·0 field notes

What This Code Means

A ground fault condition indicating zero impedance between the Fire Alarm Control Panel and ground.

Common Causes

  • 1Zero impedance between FACP and ground
  • 2Field wiring touching the cabinet or conduit
  • 3Moisture or construction dust in the enclosure
  • 4Improper connection to the building's earth ground

Resolution Steps

Connect a wire from the grounding stud in the cabinet to a known solid earth ground. Inspect all field wiring for shorts to ground and ensure the cabinet is dry and free of construction dust.