CHECK or TRBL 997: VISTA-128FBP Trouble Code | Fire Alarm Resource Center
CHECK or TRBL 997
trouble
Honeywell VISTA-128FBP
116 views
·
0 field notes
What This Code Means
Polling Loop Short circuit detected.
Common Causes
1
Short circuit on SLC/Polling Loop wiring
2
Failed device on the loop
3
Water in a device
Resolution Steps
Inspect the polling loop wiring and isolate the short circuit by disconnecting branches of the loop.
Manual References
(1)
1
honeywell
VISTA-128FBPT and VISTA-250FBPT
User Guide
2012
p. 60, 68, 3, 65, 58 +3
Open
Getting CHECK or TRBL 997 on your VISTA-128FBP?
Ask TroubleShooter AI for help
→
Field Notes
Loading field notes...
Sign in
to share a field note
Related Codes
CHECK or TRBL 974
Trouble detected on Dialer 1.
972 Earth Ground Fault
A system trouble indicating that an earth ground fault has been detected. This condition may eliminate some of the system's protection.
ALARM
Indicates that a burglary or non-fire protection zone has been faulted while the system is armed, or a 24-hour zone has been triggered.
CHECK or TRBL 970
Trouble detected on Bell 1 Output (Notification Appliance Circuit).
LO BAT accompanied by zone descriptor
A low battery condition exists in the displayed wireless transmitter.