CHECK or TRBLtrouble
Honeywell VISTA-128FBP: CHECK or TRBL
Honeywell VISTA-128FBP·1 view·0 field notes
What This Code Means
Indicates a trouble condition in the system, meaning a problem exists with specific zones, relays, peripheral devices, or system components that may eliminate some protection.
Common Causes
- 1One or more protection zones are not intact
- 2Trouble on a supervised relay (6XX, where XX = 01-32)
- 3Trouble on a peripheral device connected to the keypad terminals (8XX, where XX = 00-30)
- 4System trouble such as dialers, NACs, or ground faults (9XX, where XX = 00-99)
Resolution Steps
To silence the beeping sound for trouble conditions, press any key. Determine if the zone(s) displayed are intact (this may include Fire and Waterflow type zones) and make them so if they are not. If the problem has been corrected, key an OFF sequence (Code plus OFF) to clear the “CHECK” or “TRBL” display. If the display persists, CALL FOR SERVICE IMMEDIATELY.
Manual References(1)
Related Codes
Related Questions
How are the VISTA-128FBP bell output circuits wired and what supervision method does the system use to detect an open or short?How does the VISTA-128FBP supervise its backup battery and what does a battery trouble condition indicate?What does a ground fault trouble indicate on the VISTA-128FBP and how do I locate it?