Zone troubletrouble
Kidde FX-10: Zone trouble
Kidde FX-10·1 view·0 field notes
What This Code Means
An open or short circuit condition exists on an Initiating Device Circuit (IDC).
Common Causes
- 1Missing End-of-Line (EOL) resistor
- 2Broken field wire
- 3Device removed from base
Resolution Steps
Check the specific IDC for wiring integrity. Ensure the correct 4.7k Ohm EOL resistor is installed at the last device on the circuit.