GROUND FAULTtrouble

Notifier NFW2-100: GROUND FAULT

Notifier NFW2-100·1 view·0 field notes

What This Code Means

This condition indicates a zero impedance from the Fire Alarm Control Panel (FACP) to ground.

Common Causes

  • 1Zero impedance from the FACP to ground
  • 2Connection of a printer or PC to the FACP
  • 3Preexisting ground fault on the panel

Resolution Steps

Check for zero impedance from the FACP to ground. Do not connect a printer or PC to the NFW2-100 FACP if a ground fault exists on the control panel. To disable ground fault detection, remove jumper/shunt from JP7 with the approval of the AHJ.