GROUND FAULTtrouble
Notifier NFW2-100: GROUND FAULT
Notifier NFW2-100·1 view·0 field notes
What This Code Means
This condition indicates a zero impedance from the Fire Alarm Control Panel (FACP) to ground.
Common Causes
- 1Zero impedance from the FACP to ground
- 2Connection of a printer or PC to the FACP
- 3Preexisting ground fault on the panel
Resolution Steps
Check for zero impedance from the FACP to ground. Do not connect a printer or PC to the NFW2-100 FACP if a ground fault exists on the control panel. To disable ground fault detection, remove jumper/shunt from JP7 with the approval of the AHJ.