Notifier

NFW2-100

The Notifier NFW2-100 (FireWarden-100-2) is a cost-effective small addressable fire alarm panel supporting 1 SLC loop. Common in small commercial applications.

1 manual24 trouble codesModels: NFW2-100, NFW2-100E, FireWarden-100-2, FireWarden-100-2E

Manuals

Manuals That Reference This Model (17)

Trouble Codes

View all 24
AC_FAILThe control panel has lost primary AC power.CHARGER FAULTThe battery charger on the main circuit board has failed.COMM FAULT 1The control panel has failed 10 total attempts to communicate with the primary Central Station phone number.DIRTY1Maintenance alert indicating that a detector is near but below the allowed alarm limit.DIRTY2Maintenance alert indicating that a detector needs immediate maintenance due to being within 80% of its alarm threshold for 24 hours.DISABLInput points which are disabled do not cause an alarm or any zone activation. Disabled output points are held in the off state. All disabled points are treated as if they were in trouble.DUCT SUPERVISORYA supervisory condition has been triggered by a duct smoke detector.GROUND FAULTThis condition indicates a zero impedance from the Fire Alarm Control Panel (FACP) to ground.INV IDIncorrect device code (Type ID) has been programmed for an installed device.INVREPInvalid reply from the addressable device, indicating a hardware problem.

Specifications

SLC Loops
1
Panel Type
Addressable
NAC Circuits
4 Class B / 2 Class A
Total Points
198
Points/Loop
198 (99 det / 99 mod)
Battery (Ah)
7-18
Annunciator
Yes