NFW2-100 Trouble Codes

24 trouble codes for the Notifier NFW2-100

AC_FAIL
The control panel has lost primary AC power.
trouble
CHARGER FAULT
The battery charger on the main circuit board has failed.
trouble
COMM FAULT 1
The control panel has failed 10 total attempts to communicate with the primary Central Station phone number.
trouble
DIRTY1
Maintenance alert indicating that a detector is near but below the allowed alarm limit.
maintenance
DIRTY2
Maintenance alert indicating that a detector needs immediate maintenance due to being within 80% of its alarm threshold for 24 hours.
maintenance
DISABL
Input points which are disabled do not cause an alarm or any zone activation. Disabled output points are held in the off state. All disabled points are treated as if they were in trouble.
trouble
DUCT SUPERVISORY
A supervisory condition has been triggered by a duct smoke detector.
supervisory
GROUND FAULT
This condition indicates a zero impedance from the Fire Alarm Control Panel (FACP) to ground.
trouble
INV ID
Incorrect device code (Type ID) has been programmed for an installed device.
trouble
INVREP
Invalid reply from the addressable device, indicating a hardware problem.
trouble
LOW BATTERY
Battery voltage has fallen below the required threshold.
trouble
MEMORY FAULT
Internal system memory error.
trouble
NAC 1 FAULT
A fault condition (open or short) on Notification Appliance Circuit 1.
trouble
NO_BATTERY
The panel does not detect any batteries connected to the system.
trouble
OPEN
This trouble description indicates an open circuit condition on an addressable device or a notification appliance circuit (NAC).
trouble
SHORT
This code indicates a shorted circuit condition on an addressable device connected to the SLC loop.
trouble
SLC 1 OPEN FAULT
This condition indicates an open circuit has been detected on the Signaling Line Circuit (SLC) loop or on an addressable device connected to the loop.
trouble
SLC 1 SHORT FAULT
A short circuit condition detected on SLC Loop 1.
trouble
Active Supervisory
A condition indicating that a monitored system component is in an off-normal state, such as a sprinkler valve tamper condition.
supervisory
SW TBL
Indicates a module has failed the testing of its Class A switching relay.
trouble
TAMPER
A condition indicating that a monitored component, such as a sprinkler valve, has been moved from its normal state.
supervisory
TELCO LINE 1
Fault detected on the primary telephone line.
trouble
TEST F
Indicates a detector has failed the automatic test operation of its sensing chamber and electronics.
trouble
WATERFLOW
A device type identifier and event code for a monitor module programmed to monitor sprinkler system waterflow switches, representing a high-priority alarm condition.
alarm