MEMORY FAULT: NFW2-100 Trouble Code | Fire Alarm Resource Center
MEMORY FAULT
trouble
Notifier NFW2-100
67 views
·
0 field notes
What This Code Means
Internal system memory error.
Common Causes
1
EEPROM failure
2
Corrupted site database
3
Processor malfunction
Resolution Steps
Attempt to re-download the site program. If the fault persists, the main circuit board may need replacement.
Manual References
(1)
1
notifier
NFW2-100
Installation
2005
p. 18, 127, 107, 109, 126 +5
Open
Getting MEMORY FAULT on your NFW2-100?
Ask TroubleShooter AI for help
→
Field Notes
Loading field notes...
Sign in
to share a field note
Related Codes
INVREP
Invalid reply from the addressable device, indicating a hardware problem.
COMM FAULT 1
The control panel has failed 10 total attempts to communicate with the primary Central Station phone number.
DUCT SUPERVISORY
A supervisory condition has been triggered by a duct smoke detector.
NAC 1 FAULT
A fault condition (open or short) on Notification Appliance Circuit 1.
DIRTY2
Maintenance alert indicating that a detector needs immediate maintenance due to being within 80% of its alarm threshold for 24 hours.
Related Questions
Which Notifier intelligent detectors and modules are compatible with the NFW2-100 SLC loop?
What is the maximum SLC wiring distance and resistance limit for the NFW2-100?
How do I program the built-in DACT on the NFW2-100 for central station communication?