What This Code Means
This trouble description indicates an open circuit condition on an addressable device or a notification appliance circuit (NAC).
Common Causes
- 1Open circuit on an addressable device
- 2Broken wire or loose connection on the SLC loop
- 3NAC circuit voltage in the range of -2.3 to -2.5 VDC
- 4Missing or incorrect 4.7 k ohm End-of-Line resistor on a Style Y (Class B) NAC
Resolution Steps
Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to silence and the system Trouble LED to change from flashing to on steady. Locate the device or circuit indicated on the display and check for an open circuit condition, ensuring all wiring is intact and connections are secure.