WATERFLOW: NFW2-100 Trouble Code | Fire Alarm Resource Center
WATERFLOW
alarm
Notifier NFW2-100
83 views·0 field notes
What This Code Means
A device type identifier and event code for a monitor module programmed to monitor sprinkler system waterflow switches, representing a high-priority alarm condition.
Common Causes
1Activation of a waterflow pressure or vane switch
2Water movement within the sprinkler system piping
3Sprinkler system testing or maintenance
4Expiration of the Waterflow Retard Timer delay
Resolution Steps
Press the Acknowledge/Step or Alarm Silence key to silence the pulsing piezo. Note that the Alarm Silence key will not function if the mapped NAC outputs are programmed for nonsilenceable operation or if the Waterflow Silenceable option is set to NO in system programming. Once the waterflow condition is corrected, press the Reset key to return the system to normal operation.