Tamper Switchtrouble
Siemens MXL: Tamper Switch
Siemens MXL·0 views·0 field notes
What This Code Means
This is a security-type message for the tamper switch on the SMB-2 board when the system is selected for UL 1076 operation.
Common Causes
- 1Enclosure door is open
- 2Tamper switch on the SMB-2 board activated
- 3TSW-2 tamper switch cable disconnected from P9 on the SMB-2
- 4System selected for UL 1076 operation
Resolution Steps
Ensure the enclosure door is closed and the TSW-2 tamper switch cable is plugged into P9 on the SMB-2 board.