SK-6820 Trouble Codes

18 trouble codes for the Silent Knight SK-6820

AC Power Loss- Panel
The control panel has lost primary AC power.
trouble
An unexpected SLC device has been ID
The panel has detected a device on the SLC loop that was not programmed into the system.
trouble
Battery Trouble-Panel
The main control panel has detected a problem with its standby batteries.
trouble
Calibration trouble alert
A sensor has failed its internal calibration test.
maintenance
CO Detector Supervisory Alarm
A Carbon Monoxide detector has reached a supervisory threshold.
supervisory
DISABLE
A point or circuit has been manually taken out of service, which prevents the activation of notification appliances or alarm initiation from that specific device.
trouble
EVS Supervisory/Tamper Alarm
A supervisory or tamper condition related to the Emergency Voice System.
supervisory
GROUND FAULT
An earth ground fault occurs when the panel senses an unexpected flow of current from one or more of its terminals to the earth connection (Terminal 2).
trouble
Missing
A device or module (such as an SLC device or a 5496, 6815, or 5815XL module) is physically connected to the system but is not being recognized by the panel.
trouble
Printer is off-line trouble
The connected printer is not communicating or is set to offline mode.
trouble
Printer is out of paper trouble
The system printer has run out of paper.
trouble
Releasing Notif/Control Circuit Disabled
A circuit configured for releasing or notification has been manually disabled.
trouble
Repeater ground fault trouble
A ground fault has been detected on a repeater module.
trouble
Repeater missing trouble
A repeater module that was previously programmed is no longer communicating with the panel.
trouble
SBUS Class A supervision lost
The panel has lost the return path for a Class A SBUS circuit.
trouble
SLC Loop Shorted
A short circuit condition has been detected on the Signaling Line Circuit.
trouble
Unable to report to account trouble
The panel failed to communicate an event to the central station.
trouble
Water flow switch alarm
A water flow switch has been activated, indicating water movement in the sprinkler system.
alarm