Siemens MXL Questions
Questions and answers specific to the Siemens MXL.
Questions and answers specific to the Siemens MXL.
The MXL-IQ supports a maximum of 4 analog loops and can be networked to include up to 63 systems using the NIM-1W module (Page 12, 24) [1]. Expansion is...
The BCM-12A-C is a Battery Cutoff Module (not a charger) that automatically disconnects the system batteries if they discharge below the "Low Battery" system...
The MXL-IQ supports up to 60 intelligent devices per analog loop (Page 12) [1]. The control panel can monitor a maximum of 4 analog loops, providing a total...
To acknowledge and silence troubles on the MXL-IQ, press the TRBL ACK key on the front panel. This action silences the internal audible once all troubles (and...
Yes, the MXL supports voice evacuation through the MXLV system configuration (Page 12) [1]. The system utilizes specific modules for voice and annunciator...
The MXL-IQ can charge batteries with a capacity of up to 55 amp hours (AH) (Page 127) [1]. Listed battery models include the BP-61 (15 AH), BTX-1 (31 AH), and...
To connect the DCT-1E to an MXL system, you must provide 24 VDC power from the panel and use contact closures to trigger the communicator's five channel inputs...
On an MXL system, loop-related troubles typically refer to either network communication failures or faults on a Notification Appliance Circuit (NAC). Network...
To program an MXL system, you must use the CSG-M (AccuLINK) software to create a configuration file and then transfer it to the panel. The software is used to...
I couldn't find information for Gamewell-FCI in our manuals, but here is the ground fault procedure for the Siemens MXL-IQ. Use the TEST menu to determine if...