Loop 1 device 000: iO1000 Trouble Code | Fire Alarm Resource Center
Loop 1 device 000
trouble
Edwards EST iO1000
76 views
·
0 field notes
What This Code Means
A device on loop 1 has an address set to zero
Common Causes
1
New Signature series device not yet addressed
2
Device reset to factory defaults
Resolution Steps
Use the electronic addressing tool or panel menu to assign a valid address (1-125 or 1-250) to the device.
Manual References
(3)
1
edwards est
iO64 and iO1000
Datasheet
2020
p. 1
Open
2
edwards est
iO64 and iO1000
Datasheet
2023
p. 1
Open
3
edwards est
iO64 and iO1000
Installation
2015
p. 186, 160, 61, 187, 189 +2
Open
Getting Loop 1 device 000 on your iO1000?
Ask TroubleShooter AI for help
→
Field Notes
Loading field notes...
Sign in
to share a field note
Related Codes
Internal fault
The control panel detected an internal hardware or software error
Dialer delivery fail
The dialer failed to deliver a message to the receiver
Dialer line 1 fault
A ground fault or line fault was detected on line 1 of the dialer
Loop 1 uncfgrd trouble
A device on loop 1 that is not programmed went into trouble
Supervisory
A supervisory event is taking place on the control panel, indicating an off-normal condition on a monitored circuit or device.
Related Questions
How do I address devices on the iO1000?
How do I set up the SA-DACT dialer module in the iO1000 for dual-line DACT reporting using Contact ID format?
What Signature series devices are compatible with the iO1000 SLC loop, and can I mix legacy and newer devices on the same loop?