iO1000 Trouble Codes

27 trouble codes for the Edwards EST iO1000

Loop 1 uncfgrd trouble
A device on loop 1 that is not programmed went into trouble
trouble
Loop 1 map mismatch
The loop 1 map in RAM and the loop 1 map in the database do not match
trouble
Loop 1 over limits
There are too many devices on loop 1
trouble
Loop 1 device 000
A device on loop 1 has an address set to zero
trouble
Loop 2 fault
A short or open was detected on loop 2 affecting the communications between the panel and the devices
trouble
Loop 2 card fault
The loop 2 card is not present or it is not working
trouble
Loop 2 uncfgrd alarm
A device on loop 2 that is not programmed went into alarm
alarm
Ground fault
The panel detected a ground fault
trouble
054 Ground fault
The panel detected a ground fault condition on the system.
trouble
Battery charger
The panel detected a battery charger trouble condition
trouble
Battery low
The batteries are low
trouble
Battery missing
The battery is no longer connected
trouble
AC power
There is a problem with the panel’s AC power
trouble
Self test fault
A fault was detected while testing the panel’s internal subsystems (memory, flash, code)
trouble
Internal fault
The control panel detected an internal hardware or software error
trouble
Dialer line 1 fault
A ground fault or line fault was detected on line 1 of the dialer
trouble
Dialer delivery fail
The dialer failed to deliver a message to the receiver
trouble
IPGateway Trouble
IP Gateway configuration is invalid
trouble
NAC 1 trouble
An open or short was detected on NAC 1 or there is a problem with the EOL
trouble
Printer trouble
The printer is either offline, out of paper, or disconnected
trouble
Annunciator 1 trouble
An open or short was detected on annunciator 1
trouble
Supervisory active
A supervisory condition has been activated
supervisory
Zone maintenance alert
A maintenance alert was detected in the zone
maintenance
Common disable
A disable event is taking place on the control panel, indicating that a device, zone, or panel event has been manually deactivated.
trouble
001 Loop 1 fault
A short or open was detected on the loop affecting the communications between the panel and the devices on the loop.
trouble
Supervisory
A supervisory event is taking place on the control panel, indicating an off-normal condition on a monitored circuit or device.
supervisory
Waterflow
An input device programmed as a waterflow type has been activated, typically indicating water movement within the sprinkler system.
alarm