054 Ground faulttrouble

Edwards EST iO1000: 054 Ground fault

Edwards EST iO1000·1 view·0 field notes

What This Code Means

The panel detected a ground fault condition on the system.

Common Causes

  • 1A short between one leg of a circuit and chassis ground
  • 2A ground fault or line fault on dialer line 1 or line 2
  • 3Circuit impedance to ground between 0 to 5 kΩ

Resolution Steps

Press the menu button and choose Diagnostics. Enter a level two password. Choose Fast Ground Check. Choose Start to turn on Fast Ground Check to decrease the system ground fault check time to every four seconds. Once you solve the ground faults in the system, choose End to turn off Fast Ground Check.