What This Code Means

The panel detected a battery charger trouble condition

Common Causes

  • 1Blown battery fuse
  • 2Failed charging circuit on the main board
  • 3Extremely discharged batteries

Resolution Steps

Check the battery fuses and measure the charging voltage. If the charger is not outputting the correct voltage, the main board may need replacement.