Battery chargertrouble
Edwards EST iO1000: Battery charger
Edwards EST iO1000·0 views·0 field notes
What This Code Means
The panel detected a battery charger trouble condition
Common Causes
- 1Blown battery fuse
- 2Failed charging circuit on the main board
- 3Extremely discharged batteries
Resolution Steps
Check the battery fuses and measure the charging voltage. If the charger is not outputting the correct voltage, the main board may need replacement.