What This Code Means
An open or short was detected on annunciator 1
Common Causes
- 1RS-485 communication wire break
- 2Loss of 24V power to the annunciator
- 3Incorrect annunciator address
Resolution Steps
Check the wiring between the panel and the annunciator. Verify the annunciator has power and the address dipswitches are set correctly.