Loop is too long or attenuation too high
troubleESSER FlexES
50 views·0 field notes
What This Code Means
Signal strength is too low due to excessive loop length or high cable resistance.
Common Causes
- 1Loop length exceeds maximum limits
- 2Incorrect cable type used (e.g., non-IBM or non-transmission cable)
- 3High resistance connections
Resolution Steps
Verify loop length and resistance (max 70-100 ohms/km depending on cable); reduce length or upgrade cable if necessary.
Manual References(1)
Related Codes
Related Questions
How do I reset a fault condition on the Esser FlexES panel after replacing a detector on the loop?What do the common FlexES error codes mean, such as Loop Fault, Short Circuit, and Device Not Responding?What is the procedure for performing a walk test on the FlexES panel to verify detector and module operation?