Loop is too long or attenuation too hightrouble
ESSER FlexES: Loop is too long or attenuation too high
ESSER FlexES·0 views·0 field notes
What This Code Means
Signal strength is too low due to excessive loop length or high cable resistance.
Common Causes
- 1Loop length exceeds maximum limits
- 2Incorrect cable type used (e.g., non-IBM or non-transmission cable)
- 3High resistance connections
Resolution Steps
Verify loop length and resistance (max 70-100 ohms/km depending on cable); reduce length or upgrade cable if necessary.
Manual References(1)
Related Codes
Related Questions
How do I reset a fault condition on the Esser FlexES panel after replacing a detector on the loop?How do I set up cause-and-effect programming on the FlexES panel to link detector zones to NAC outputs?What are the compatible battery specifications for the FlexES panel, and what is the procedure for battery replacement?