ESSER

FlexES

The Esser FlexES is a modular intelligent fire alarm control panel widely used in international markets. Offers flexible configuration and networking capabilities.

1 manual14 trouble codesModels: FlexES, FlexES Control, FX808382, FX808384

Manuals

Manuals That Reference This Model (1)

Trouble Codes

View all 14
Battery fault (excessive contact resistance)The system has detected excessive resistance (> 200 mOhm) at the battery terminals or cables.Battery FaultThe FACP indicates a fault when battery resistance is too high, voltage drops below the discharging limit, or a connection/fuse issue is detected.EARTH FAULTThe system has detected an unintended connection to ground or an incorrect configuration of the earth fault detection jumpers on multiple power supply modules.essernet connection interruptionA break or wiring error has been detected in the essernet communication loop.Panel or essernet device not receiving powerA device on the essernet is not receiving power or is completely disconnected.Damaging the line (essernet module 500 kBd)Physical damage to the essernet 500 kBd line, often due to installation errors.Loop is too long or attenuation too highSignal strength is too low due to excessive loop length or high cable resistance.Hardware errorInternal hardware failure detected within the essernet module.Fault in the mains power supplyThe primary 230 V AC power source is missing or has failed.>Short circuit/interruption<A condition indicating a short circuit or interruption on the connection line, which may cause the system to isolate segments of the loop using group separators.

Specifications

SLC Loops
1-18 (model dependent)
Panel Type
Addressable
NAC Circuits
4
Total Points
127-2,286
Points/Loop
127
Battery (Ah)
12-24
Annunciator
Yes

Related Questions