FlexES Trouble Codes

14 trouble codes for the ESSER FlexES

Battery fault (excessive contact resistance)
The system has detected excessive resistance (> 200 mOhm) at the battery terminals or cables.
trouble
Battery Fault
The FACP indicates a fault when battery resistance is too high, voltage drops below the discharging limit, or a connection/fuse issue is detected.
trouble
EARTH FAULT
The system has detected an unintended connection to ground or an incorrect configuration of the earth fault detection jumpers on multiple power supply modules.
trouble
essernet connection interruption
A break or wiring error has been detected in the essernet communication loop.
trouble
Panel or essernet device not receiving power
A device on the essernet is not receiving power or is completely disconnected.
trouble
Damaging the line (essernet module 500 kBd)
Physical damage to the essernet 500 kBd line, often due to installation errors.
trouble
Loop is too long or attenuation too high
Signal strength is too low due to excessive loop length or high cable resistance.
trouble
Hardware error
Internal hardware failure detected within the essernet module.
trouble
Fault in the mains power supply
The primary 230 V AC power source is missing or has failed.
trouble
>Short circuit/interruption<
A condition indicating a short circuit or interruption on the connection line, which may cause the system to isolate segments of the loop using group separators.
trouble
SYS fault. essernet® cont: xx
Incorrect setting of the essernet address on the DIL switch of the essernet module.
trouble
Tamper contact
The system has detected that a housing panel or door has been opened or tampered with.
supervisory
Tamper contact
The tamper contact is used to monitor whether the control panel's housing has been opened and can be used to automatically deactivate components for servicing.
trouble
Wrong address setting
The essernet module has detected an invalid or conflicting address configuration after a restart.
trouble