FlexES Trouble Codes
14 trouble codes for the ESSER FlexES
Battery fault (excessive contact resistance)Battery FaultEARTH FAULTessernet connection interruptionPanel or essernet device not receiving powerDamaging the line (essernet module 500 kBd)Loop is too long or attenuation too highHardware errorFault in the mains power supply>Short circuit/interruption<SYS fault. essernet® cont: xxTamper contactTamper contactWrong address setting
The system has detected excessive resistance (> 200 mOhm) at the battery terminals or cables.
trouble
The FACP indicates a fault when battery resistance is too high, voltage drops below the discharging limit, or a connection/fuse issue is detected.
trouble
The system has detected an unintended connection to ground or an incorrect configuration of the earth fault detection jumpers on multiple power supply modules.
trouble
A break or wiring error has been detected in the essernet communication loop.
trouble
A device on the essernet is not receiving power or is completely disconnected.
trouble
Physical damage to the essernet 500 kBd line, often due to installation errors.
trouble
Signal strength is too low due to excessive loop length or high cable resistance.
trouble
Internal hardware failure detected within the essernet module.
trouble
The primary 230 V AC power source is missing or has failed.
trouble
A condition indicating a short circuit or interruption on the connection line, which may cause the system to isolate segments of the loop using group separators.
trouble
Incorrect setting of the essernet address on the DIL switch of the essernet module.
trouble
The system has detected that a housing panel or door has been opened or tampered with.
supervisory
The tamper contact is used to monitor whether the control panel's housing has been opened and can be used to automatically deactivate components for servicing.
trouble
The essernet module has detected an invalid or conflicting address configuration after a restart.
trouble